Modbus protocol

Modbus is a data communications protocol originally published by Modicon in 1979 for use with its programmable logic controllers. Modbus has become a de facto standard communication protocol and is now a commonly available means of connecting industrial electronic devices.

Dostupná řešení




This template is for Zabbix version: 7.2

Source: https://git.zabbix.com/projects/ZBX/repos/zabbix/browse/src/go/plugins/modbus?at=release/7.2

Modbus plugin

This plugin provides a native solution for monitoring modbus devices by Zabbix. The plugin can monitor several modbus devices simultaneously via Zabbix agent 2. Both TCP and RTU connections are supported.

Installation

The plugin is supplied as part of the Zabbix Agent 2 and does not require any special installation steps. Once Zabbix Agent 2 is installed, the plugin is ready to work. Now you need to make sure that a modbus device is available for connection and configure monitoring.

Configuration

Open the Zabbix Agent configuration file (zabbix_agent2.conf) and set the required parameters.

Plugins.Modbus.Timeout — request execution timeout (how long to wait for a request to complete before shutting it down).
Default value: equals the global 'Timeout' (configuration parameter set in zabbix_agent2.conf).
Limits: 1-30

Named sessions

Named sessions allow you to define specific parameters for each instance of modbus device. Currently, only three parameters are supported: Endpoint, SlaveID and Timeout (if certain parameter is not specified for a named session, a value from key will be used).

Example:
If you have two instances: "MB1" and "MB2", the following options have to be added to the agent configuration:

Plugins.Modbus.Sessions.MB1.Endpoint=tcp://127.0.0.1:502
Plugins.Modbus.Sessions.MB1.SlaveID=20
Plugins.Modbus.Sessions.MB1.Timeout=2
Plugins.Modbus.Sessions.MB2.Endpoint=rtu://com1:9600:8n1
Plugins.Modbus.Sessions.MB2.SlaveID=40
Plugins.Modbus.Sessions.MB2.Timeout=4

Now, these names can be used as connStrings in keys instead of URIs:

modbus.get[MB1]
modbus.get[MB2,,,30001,1,uint64,le,0]

Parameters priority

Zabbix checks parameters in the following order:

  1. Item key parameters (checked first).
  2. Named session parameters in configuration file (Plugins.Modbus.Sessions.<sessionName>.<parameter>). Checked only if values provided in a key parameters are empty. →

Supported keys

modbus.get[endpoint,slaveid,function,address,count,type,endianness,offset] — receive value from modbus device Params:

  • endpoint — tcp or rtu connection string. tcp://localhost:511 rtu://COM1:9600:8n1
  • slaveid — Modbus address of the device. Optional.
  • function — 1,2,3,4 modbus read functions. Optional.
  • address — Address of first registry , coil or input. Default 00001. Optional.
  • count — count of number for return. Default 1. Optional.
  • type — acceptable values: bit, int8, uint8, uint16, int16, uint32, int32, float, uint64 and double. Default bit or uint8. Optional.
  • endianness — acceptable values: be, le, mbe, mle. Optional.
  • offset — Number of registers or bits, starting from 'address', the result of which will be discarded. Optional. Returns: Array of numbers in JSON format.

Troubleshooting

The plugin uses Zabbix Agent logs. To receive more detailed information about logged events, consider increasing a debug level of Zabbix Agent.