APC UPS SNMP

Overview

For Zabbix version: 6.2 and higher
The template to monitor APC UPS with NMC by Zabbix SNMP agent. Note: please, use the latest version of the firmware for your NMC in order for the template to work correctly.

Setup

See Zabbix template operation for basic instructions.

1. Create a host for APC UPS management IP as SNMPv2 interface.

2. Link the template to the host.

3. Customize macro values if needed.

Zabbix configuration

No specific Zabbix configuration is required.

Macros used

Name Description Default
{$BATTERY.CAPACITY.MIN.WARN}

Minimum battery capacity percentage for trigger expression.

50
{$BATTERY.TEMP.MAX.WARN}

Maximum battery temperature for trigger expression.

55
{$SNMP.TIMEOUT}

The time interval for SNMP agent availability trigger expression.

5m
{$TIME.PERIOD}

Time period for trigger expression.

15m
{$UPS.INPUT_FREQ.MAX.WARN}

Maximum input frequency for trigger expression.

50.3
{$UPS.INPUT_FREQ.MIN.WARN}

Minimum input frequency for trigger expression.

49.7
{$UPS.INPUT_VOLT.MAX.WARN}

Maximum input voltage for trigger expression.

243
{$UPS.INPUT_VOLT.MIN.WARN}

Minimum input voltage for trigger expression.

197
{$UPS.OUTPUT.MAX.WARN}

Maximum output load in % for trigger expression.

80

Template links

There are no template links in this template.

Discovery rules

Name Description Type Key and additional info
External bad battery packs discovery

Discovery of the number of external defective battery packs.

SNMP battery.packs.bad.discovery
External battery packs discovery SNMP battery.packs.discovery

Filter:

AND

- {#CARTRIDGE_STATUS} NOT_MATCHES_REGEX ^$

External sensor port 1 discovery

uioSensorStatusTable

SNMP external.sensor1.discovery

Overrides:

Temp
- {#EXTERNAL_SENSOR1_NAME} MATCHES_REGEX Temp
- ITEM_PROTOTYPE LIKE Humidity - NO_DISCOVER

External sensor port 2 discovery

uioSensorStatusTable

SNMP external.sensor2.discovery

Overrides:

Temp
- {#EXTERNAL_SENSOR2_NAME} MATCHES_REGEX Temp
- ITEM_PROTOTYPE LIKE Humidity - NO_DISCOVER

Input phases discovery

The input phase identifier. OID upsPhaseInputPhaseIndex.1.1

SNMP input.phases.discovery
Output phases discovery

The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1

SNMP output.phases.discovery

Items collected

Group Name Description Type Key and additional info
General Model

MIB: PowerNet-MIB

The UPS model name (e.g. 'APC Smart-UPS 600').

SNMP system.model[upsBasicIdentModel]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

General Serial number

MIB: PowerNet-MIB

An 8-character string identifying the serial number of

the UPS internal microprocessor. This number is set at

the factory. NOTE: This number does NOT correspond to

the serial number on the rear of the UPS.

SNMP system.sn[upsAdvIdentSerialNumber]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

General SNMP traps (fallback)

The item is used to collect all SNMP traps unmatched by other snmptrap items

SNMP_TRAP snmptrap.fallback
General System location

MIB: SNMPv2-MIB

The physical location of this node (e.g., telephone closet,</p><p>3rd floor'). If the location is unknown, the value is the zero-length string.</p> |SNMP |system.location[sysLocation.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT:6h`

General System contact details

MIB: SNMPv2-MIB

The textual identification of the contact person for this managed

node, together with information on how to contact this person. If no contact

information is known, the value is the zero-length string.

SNMP system.contact[sysContact.0]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 12h

General System object ID

MIB: SNMPv2-MIB

The vendor's authoritative identification of the network management

subsystem contained in the entity. This value is allocated within the SMI enterprises

subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determiningwhat</p><p>kind of box' is being managed. For example, if vendorFlintstones, Inc.' was

assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1

to its Fred Router'.</p> |SNMP |system.objectid[sysObjectID.0]<p>**Preprocessing**:</p><p>- DISCARD_UNCHANGED_HEARTBEAT:6h`

General System name

MIB: SNMPv2-MIB

An administratively-assigned name for this managed node.By

convention, this is the node's fully-qualified domain name. If the name is unknown,

the value is the zero-length string.

SNMP system.name[sysName.0]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

General System description

MIB: SNMPv2-MIB

A textual description of the entity. This value should

include the full name and version identification of the system's hardware type, software operating-system, and

networking software.

SNMP system.descr[sysDescr.0]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 12h

General {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number

MIB: PowerNet-MIB

The battery pack serial number.

SNMP system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status Battery status

MIB: PowerNet-MIB

The status of the UPS batteries. A batteryLow(3) value

indicates the UPS will be unable to sustain the current

load, and its services will be lost if power is not restored.

The amount of run time in reserve at the time of low battery

can be configured by the upsAdvConfigLowBatteryRunTime.

A batteryInFaultCondition(4)value indicates that a battery

installed has an internal error condition.

SNMP battery.status[upsBasicBatteryStatus]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status Battery capacity

MIB: PowerNet-MIB

The remaining battery capacity expressed as

percentage of full capacity.

SNMP battery.capacity[upsHighPrecBatteryCapacity]

Preprocessing:

- MULTIPLIER: 0.1

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status Battery runtime remaining

MIB: PowerNet-MIB

The UPS battery run time remaining before battery

exhaustion.

SNMP battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]

Preprocessing:

- MULTIPLIER: 0.01

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status Battery voltage

MIB: PowerNet-MIB

The actual battery bus voltage in Volts.

SNMP battery.voltage[upsHighPrecBatteryActualVoltage]

Preprocessing:

- MULTIPLIER: 0.1

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status Battery last replace date

MIB: PowerNet-MIB

The date when the UPS system's batteries were last replaced

in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value

is originally set at the factory. When the UPS batteries

are replaced, this value should be reset by the administrator.

For Symmetra PX 250/500 this OID is read-only and is configurable in the local display only.

SNMP battery.last_replace_date[upsBasicBatteryLastReplaceDate]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status Battery replace indicator

MIB: PowerNet-MIB

Indicates whether the UPS batteries need replacement.

SNMP battery.replace_indicator[upsAdvBatteryReplaceIndicator]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status External battery packs count

MIB: PowerNet-MIB

The number of external battery packs connected to the UPS. If

the UPS does not use smart cells then the agent reports

ERROR_NO_SUCH_NAME.

SNMP battery.external_packs_count[upsAdvBatteryNumOfBattPacks]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status Battery temperature

MIB: PowerNet-MIB

The current internal UPS temperature in Celsius.

Temperatures below zero read as 0.

SNMP battery.temperature[upsHighPrecBatteryTemperature]

Preprocessing:

- MULTIPLIER: 0.1

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status Input voltage

MIB: PowerNet-MIB

The current utility line voltage in VAC.

SNMP input.voltage[upsHighPrecInputLineVoltage]

Preprocessing:

- MULTIPLIER: 0.1

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status Input frequency

MIB: PowerNet-MIB

The current input frequency to the UPS system in Hz.

SNMP input.frequency[upsHighPrecInputFrequency]

Preprocessing:

- MULTIPLIER: 0.1

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status Input fail cause

MIB: PowerNet-MIB

The reason for the occurrence of the last transfer to UPS

battery power. The variable is set to:

- noTransfer(1) -- if there is no transfer yet.

- highLineVoltage(2) -- if the transfer to battery is caused

by an over voltage greater than the high transfer voltage.

- brownout(3) -- if the duration of the outage is greater than

five seconds and the line voltage is between 40% of the

rated output voltage and the low transfer voltage.

- blackout(4) -- if the duration of the outage is greater than five

seconds and the line voltage is between 40% of the rated

output voltage and ground.

- smallMomentarySag(5) -- if the duration of the outage is less

than five seconds and the line voltage is between 40% of the

rated output voltage and the low transfer voltage.

- deepMomentarySag(6) -- if the duration of the outage is less

than five seconds and the line voltage is between 40% of the

rated output voltage and ground. The variable is set to

- smallMomentarySpike(7) -- if the line failure is caused by a

rate of change of input voltage less than ten volts per cycle.

- largeMomentarySpike(8) -- if the line failure is caused by

a rate of change of input voltage greater than ten volts per cycle.

- selfTest(9) -- if the UPS was commanded to do a self test.

- rateOfVoltageChange(10) -- if the failure is due to the rate of change of

the line voltage.

SNMP input.fail[upsAdvInputLineFailCause]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status Output voltage

MIB: PowerNet-MIB

The output voltage of the UPS system in VAC.

SNMP output.voltage[upsHighPrecOutputVoltage]

Preprocessing:

- MULTIPLIER: 0.1

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status Output load

MIB: PowerNet-MIB

The current UPS load expressed as percentage

of rated capacity.

SNMP output.load[upsHighPrecOutputLoad]

Preprocessing:

- MULTIPLIER: 0.1

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status Output current

MIB: PowerNet-MIB

The current in amperes drawn by the load on the UPS.

SNMP output.current[upsHighPrecOutputCurrent]

Preprocessing:

- MULTIPLIER: 0.1

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status Output status

MIB: PowerNet-MIB

The current state of the UPS. If the UPS is unable to

determine the state of the UPS this variable is set

to unknown(1).

During self-test most UPSes report onBattery(3) but

some that support it will report onBatteryTest(15).

To determine self-test status across all UPSes, refer

to the upsBasicStateOutputState OID.

SNMP output.status[upsBasicOutputStatus]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status Uptime

MIB: SNMPv2-MIB

The time (in hundredths of a second) since the network management

portion of the system was last re-initialized.

SNMP system.uptime[sysUpTime.0]

Preprocessing:

- MULTIPLIER: 0.01

Status SNMP agent availability

Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.

Possible value:

0 - not available

1 - available

2 - unknown

INTERNAL zabbix[host,snmp,available]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status {#PHASEINDEX}: Phase input voltage

MIB: PowerNet-MIB

The input voltage in VAC, or -1 if it's unsupported

by this UPS.

SNMP phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status {#PHASEINDEX}: Phase input current

MIB: PowerNet-MIB

The input current in 0.1 amperes, or -0.1 if it's

unsupported by this UPS.

SNMP phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]

Preprocessing:

- MULTIPLIER: 0.1

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status {#PHASEINDEX}: Phase output voltage

MIB: PowerNet-MIB

The output voltage in VAC, or -1 if it's unsupported

by this UPS.

SNMP phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status {#PHASEINDEX}: Phase output current

MIB: PowerNet-MIB

The output current in 0.1 amperes drawn

by the load on the UPS, or -1 if it's unsupported

by this UPS.

SNMP phase.output.current[upsPhaseOutputCurrent.1.1.{#PHASEINDEX}]

Preprocessing:

- MULTIPLIER: 0.1

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status {#PHASEINDEX}: Phase output load, %

MIB: PowerNet-MIB

The percentage of the UPS load capacity in VA at

redundancy @ (n + x) presently being used on this

output phase, or -1 if it's unsupported by this UPS.

SNMP phase.output.load.percent[upsPhaseOutputPercentLoad.1.1.{#PHASEINDEX}]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status

MIB: PowerNet-MIB

The battery cartridge status.

bit 0 Disconnected

bit 1 Overvoltage

bit 2 NeedsReplacement

bit 3 OvertemperatureCritical

bit 4 Charger

bit 5 TemperatureSensor

bit 6 BusSoftStart

bit 7 OvertemperatureWarning

bit 8 GeneralError

bit 9 Communication

bit 10 DisconnectedFrame

bit 11 FirmwareMismatch

SNMP battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery temperature

MIB: PowerNet-MIB

The battery pack temperature in Celsius.

SNMP battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]

Preprocessing:

- MULTIPLIER: 0.1

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery estimated replace date

MIB: PowerNet-MIB

The battery cartridge estimated battery replace date.

SNMP battery.estimated_replace_date[upsHighPrecBatteryPackCartridgeReplaceDate.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health

MIB: PowerNet-MIB

The battery cartridge health.

bit 0 Battery lifetime okay

bit 1 Battery lifetime near end, order replacement cartridge

bit 2 Battery lifetime exceeded, replace battery

bit 3 Battery lifetime near end acknowledged, order replacement cartridge

bit 4 Battery lifetime exceeded acknowledged, replace battery

bit 5 Battery measured lifetime near end, order replacement cartridge

bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge

SNMP battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status {#SNMPINDEX}: External battery packs bad

MIB: PowerNet-MIB

The number of external battery packs connected to the UPS that

are defective. If the UPS does not use smart cells then the

agent reports ERROR_NO_SUCH_NAME.

SNMP battery.external_packs_bad[upsAdvBatteryNumOfBadBattPacks.{#SNMPINDEX}]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status {#EXTERNAL_SENSOR1_NAME}: Temperature sensor

MIB: PowerNet-MIB

The sensor's current temperature reading in Celsius.

-1 indicates an invalid reading due to lost communications.

SNMP external.sensor.temperature[uioSensorStatusTemperatureDegC.1.{#SNMPINDEX}]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status {#EXTERNAL_SENSOR1_NAME}: Humidity sensor

MIB: PowerNet-MIB

The sensor's current humidity reading - a relative humidity

percentage. -1 indicates an invalid reading due to either a

sensor that doesn't read humidity or lost communications.

SNMP external.sensor.humidity[uioSensorStatusHumidity.1.{#SNMPINDEX}]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status {#EXTERNAL_SENSOR1_NAME}: Sensor alarm status

MIB: PowerNet-MIB

The alarm status of the sensor. Possible values:

uioNormal (1),

uioWarning (2),

uioCritical (3),

sensorStatusNotApplicable (4)

SNMP external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status {#EXTERNAL_SENSOR2_NAME}: Temperature sensor

MIB: PowerNet-MIB

The sensor's current temperature reading in Celsius.

-1 indicates an invalid reading due to lost communications.

SNMP external.sensor.temperature[uioSensorStatusTemperatureDegC.2.{#SNMPINDEX}]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status {#EXTERNAL_SENSOR2_NAME}: Humidity sensor

MIB: PowerNet-MIB

The sensor's current humidity reading - a relative humidity

percentage. -1 indicates an invalid reading due to either a

sensor that doesn't read humidity or lost communications.

SNMP external.sensor.humidity[uioSensorStatusHumidity.2.{#SNMPINDEX}]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Status {#EXTERNAL_SENSOR2_NAME}: Sensor alarm status

MIB: PowerNet-MIB

The alarm status of the sensor. Possible values:

uioNormal (1),

uioWarning (2),

uioCritical (3),

sensorStatusNotApplicable (4)

SNMP external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}]

Preprocessing:

- DISCARD_UNCHANGED_HEARTBEAT: 6h

Triggers

Name Description Expression Severity Dependencies and additional info
System name has changed

System name has changed. Ack to close.

last(/APC UPS SNMP/system.name[sysName.0],#1)<>last(/APC UPS SNMP/system.name[sysName.0],#2) and length(last(/APC UPS SNMP/system.name[sysName.0]))>0 INFO

Manual close: YES

Battery has an internal error condition

A battery installed has an internal error condition.

last(/APC UPS SNMP/battery.status[upsBasicBatteryStatus])=4 AVERAGE
Battery is Low

The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.

last(/APC UPS SNMP/battery.status[upsBasicBatteryStatus])=3 AVERAGE
Battery has low capacity

-

last(/APC UPS SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN} HIGH
Battery needs replacement

A battery installed has an internal error condition.

last(/APC UPS SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2 HIGH
Battery has high temperature

-

min(/APC UPS SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN} HIGH
Unacceptable input voltage

-

min(/APC UPS SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}) HIGH
Unacceptable input frequency

-

min(/APC UPS SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN}) HIGH
Output load is high

A battery installed has an internal error condition.

min(/APC UPS SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN} HIGH
UPS is Timed Sleeping

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=5 AVERAGE
UPS is Switched Bypass

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=9 AVERAGE
UPS is Software Bypass

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=6 AVERAGE
UPS is Sleeping Until Power Return

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=11 AVERAGE
UPS is Rebooting

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=8 AVERAGE
UPS is On Smart Trim

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=12 AVERAGE
UPS is on Smart Boost

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=4 AVERAGE
UPS is on battery

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=3 AVERAGE
UPS is Off

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=7 AVERAGE
UPS is Emergency Static Bypass

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=16 AVERAGE
UPS is Hardware Failure Bypass

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=10 AVERAGE
has been restarted

Uptime is less than 10 minutes.

last(/APC UPS SNMP/system.uptime[sysUpTime.0])<10m WARNING

Manual close: YES

Depends on:

- No SNMP data collection

No SNMP data collection

SNMP is not available for polling. Please check device connectivity and SNMP settings.

max(/APC UPS SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0 WARNING
{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage

-

min(/APC UPS SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN} HIGH
{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage

-

min(/APC UPS SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN} HIGH
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay

The battery cartridge status:

bit 0 Disconnected

bit 1 Overvoltage

bit 2 NeedsReplacement

bit 3 OvertemperatureCritical

bit 4 Charger

bit 5 TemperatureSensor

bit 6 BusSoftStart

bit 7 OvertemperatureWarning

bit 8 GeneralError

bit 9 Communication

bit 10 DisconnectedFrame

bit 11 FirmwareMismatch

find(/APC UPS SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0 WARNING
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature

-

min(/APC UPS SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN} HIGH
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay

The battery cartridge health.

bit 0 Battery lifetime okay

bit 1 Battery lifetime near end, order replacement cartridge

bit 2 Battery lifetime exceeded, replace battery

bit 3 Battery lifetime near end acknowledged, order replacement cartridge

bit 4 Battery lifetime exceeded acknowledged, replace battery

bit 5 Battery measured lifetime near end, order replacement cartridge

bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge

find(/APC UPS SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1 WARNING
{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable

The external sensor does not work or is not connected.

last(/APC UPS SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4 INFO
{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning

The external sensor has returned a value greater than the warning threshold.

last(/APC UPS SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2 AVERAGE
{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical

The external sensor has returned a value greater than the critical threshold.

last(/APC UPS SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3 HIGH
{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable

The external sensor does not work or is not connected.

last(/APC UPS SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4 INFO
{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning

The external sensor has returned a value greater than the warning threshold.

last(/APC UPS SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2 AVERAGE
{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical

The external sensor has returned a value greater than the critical threshold.

last(/APC UPS SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3 HIGH

Feedback

Please report any issues with the template at https://support.zabbix.com