Source: https://git.zabbix.com/projects/ZBX/repos/zabbix/browse/templates/power/apc/apc_ups_smart_srt_5000_snmp

APC Smart-UPS SRT 5000 by SNMP

Overview

The template to monitor APC Smart-UPS SRT 5000 by Zabbix SNMP agent. Note: please, use the latest version of the firmware for your NMC in order for the template to work correctly.

Requirements

Zabbix version: 7.2 and higher.

Tested versions

This template has been tested on:

  • APC Smart-UPS SRT 5000

Configuration

Zabbix should be configured according to the instructions in the Templates out of the box section.

Setup

1. Create a host for APC Smart-UPS SRT 5000 management IP as SNMPv2 interface.

2. Link the template to the host.

3. Customize macro values if needed.

Macros used

Name Description Default
{$BATTERY.TEMP.MAX.WARN}

Maximum battery temperature for trigger expression.

55
{$BATTERY.CAPACITY.MIN.WARN}

Minimum battery capacity percentage for trigger expression.

50
{$UPS.OUTPUT.MAX.WARN}

Maximum output load in % for trigger expression.

80
{$UPS.INPUT_FREQ.MIN.WARN}

Minimum input frequency for trigger expression.

49.7
{$UPS.INPUT_FREQ.MAX.WARN}

Maximum input frequency for trigger expression.

50.3
{$UPS.INPUT_VOLT.MIN.WARN}

Minimum input voltage for trigger expression.

197
{$UPS.INPUT_VOLT.MAX.WARN}

Maximum input voltage for trigger expression.

243
{$TIME.PERIOD}

Time period for trigger expression.

15m
{$SNMP.TIMEOUT}

The time interval for SNMP agent availability trigger expression.

5m

Items

Name Description Type Key and additional info
Model

MIB: PowerNet-MIB

The UPS model name (e.g. 'APC Smart-UPS 600').

SNMP agent system.model[upsBasicIdentModel]

Preprocessing

  • Discard unchanged with heartbeat: 6h

Serial number

MIB: PowerNet-MIB

An 8-character string identifying the serial number of

the UPS internal microprocessor. This number is set at

the factory. NOTE: This number does NOT correspond to

the serial number on the rear of the UPS.

SNMP agent system.sn[upsAdvIdentSerialNumber]

Preprocessing

  • Discard unchanged with heartbeat: 6h

Battery status

MIB: PowerNet-MIB

The status of the UPS batteries. A batteryLow(3) value

indicates the UPS will be unable to sustain the current

load, and its services will be lost if power is not restored.

The amount of run time in reserve at the time of low battery

can be configured by the upsAdvConfigLowBatteryRunTime.

A batteryInFaultCondition(4)value indicates that a battery

installed has an internal error condition.

SNMP agent battery.status[upsBasicBatteryStatus]

Preprocessing

  • Discard unchanged with heartbeat: 6h

Battery capacity

MIB: PowerNet-MIB

The remaining battery capacity expressed as

percentage of full capacity.

SNMP agent battery.capacity[upsHighPrecBatteryCapacity]

Preprocessing

  • Custom multiplier: 0.1

  • Discard unchanged with heartbeat: 6h

Battery runtime remaining

MIB: PowerNet-MIB

The UPS battery run time remaining before battery

exhaustion.

SNMP agent battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]

Preprocessing

  • Custom multiplier: 0.01

  • Discard unchanged with heartbeat: 6h

Battery voltage

MIB: PowerNet-MIB

The actual battery bus voltage in Volts.

SNMP agent battery.voltage[upsHighPrecBatteryActualVoltage]

Preprocessing

  • Custom multiplier: 0.1

  • Discard unchanged with heartbeat: 6h

Battery last replace date

MIB: PowerNet-MIB

The date when the UPS system's batteries were last replaced

in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value

is originally set at the factory. When the UPS batteries

are replaced, this value should be reset by the administrator.

For Symmetra PX 250/500 this OID is read-only and is configurable in the local display only.

SNMP agent battery.last_replace_date[upsBasicBatteryLastReplaceDate]

Preprocessing

  • Discard unchanged with heartbeat: 6h

Battery replace indicator

MIB: PowerNet-MIB

Indicates whether the UPS batteries need replacement.

SNMP agent battery.replace_indicator[upsAdvBatteryReplaceIndicator]

Preprocessing

  • Discard unchanged with heartbeat: 6h

External battery packs count

MIB: PowerNet-MIB

The number of external battery packs connected to the UPS. If

the UPS does not use smart cells then the agent reports

ERROR_NO_SUCH_NAME.

SNMP agent battery.external_packs_count[upsAdvBatteryNumOfBattPacks]

Preprocessing

  • Discard unchanged with heartbeat: 6h

Battery temperature

MIB: PowerNet-MIB

The current internal UPS temperature in Celsius.

Temperatures below zero read as 0.

SNMP agent battery.temperature[upsHighPrecBatteryTemperature]

Preprocessing

  • Custom multiplier: 0.1

  • Discard unchanged with heartbeat: 6h

Input voltage

MIB: PowerNet-MIB

The current utility line voltage in VAC.

SNMP agent input.voltage[upsHighPrecInputLineVoltage]

Preprocessing

  • Custom multiplier: 0.1

  • Discard unchanged with heartbeat: 6h

Input frequency

MIB: PowerNet-MIB

The current input frequency to the UPS system in Hz.

SNMP agent input.frequency[upsHighPrecInputFrequency]

Preprocessing

  • Custom multiplier: 0.1

  • Discard unchanged with heartbeat: 6h

Input fail cause

MIB: PowerNet-MIB

The reason for the occurrence of the last transfer to UPS

battery power. The variable is set to:

- noTransfer(1) -- if there is no transfer yet.

- highLineVoltage(2) -- if the transfer to battery is caused

by an over voltage greater than the high transfer voltage.

- brownout(3) -- if the duration of the outage is greater than

five seconds and the line voltage is between 40% of the

rated output voltage and the low transfer voltage.

- blackout(4) -- if the duration of the outage is greater than five

seconds and the line voltage is between 40% of the rated

output voltage and ground.

- smallMomentarySag(5) -- if the duration of the outage is less

than five seconds and the line voltage is between 40% of the

rated output voltage and the low transfer voltage.

- deepMomentarySag(6) -- if the duration of the outage is less

than five seconds and the line voltage is between 40% of the

rated output voltage and ground. The variable is set to

- smallMomentarySpike(7) -- if the line failure is caused by a

rate of change of input voltage less than ten volts per cycle.

- largeMomentarySpike(8) -- if the line failure is caused by

a rate of change of input voltage greater than ten volts per cycle.

- selfTest(9) -- if the UPS was commanded to do a self test.

- rateOfVoltageChange(10) -- if the failure is due to the rate of change of

the line voltage.

SNMP agent input.fail[upsAdvInputLineFailCause]

Preprocessing

  • Discard unchanged with heartbeat: 6h

Output voltage

MIB: PowerNet-MIB

The output voltage of the UPS system in VAC.

SNMP agent output.voltage[upsHighPrecOutputVoltage]

Preprocessing

  • Custom multiplier: 0.1

  • Discard unchanged with heartbeat: 6h

Output load

MIB: PowerNet-MIB

The current UPS load expressed as percentage

of rated capacity.

SNMP agent output.load[upsHighPrecOutputLoad]

Preprocessing

  • Custom multiplier: 0.1

  • Discard unchanged with heartbeat: 6h

Output current

MIB: PowerNet-MIB

The current in amperes drawn by the load on the UPS.

SNMP agent output.current[upsHighPrecOutputCurrent]

Preprocessing

  • Custom multiplier: 0.1

  • Discard unchanged with heartbeat: 6h

Output status

MIB: PowerNet-MIB

The current state of the UPS. If the UPS is unable to

determine the state of the UPS this variable is set

to unknown(1).

During self-test most UPSes report onBattery(3) but

some that support it will report onBatteryTest(15).

To determine self-test status across all UPSes, refer

to the upsBasicStateOutputState OID.

SNMP agent output.status[upsBasicOutputStatus]

Preprocessing

  • Discard unchanged with heartbeat: 6h

Uptime (network)

MIB: SNMPv2-MIB

The time (in hundredths of a second) since the network management portion of the system was last re-initialized.

SNMP agent system.net.uptime[sysUpTime.0]

Preprocessing

  • Custom multiplier: 0.01

Uptime (hardware)

MIB: HOST-RESOURCES-MIB

The amount of time since this host was last initialized. Note that this is different from sysUpTime in the SNMPv2-MIB [RFC1907] because sysUpTime is the uptime of the network management portion of the system.

SNMP agent system.hw.uptime[hrSystemUptime.0]

Preprocessing

  • Check for not supported value: any error

    ⛔️Custom on fail: Set value to: 0

  • Custom multiplier: 0.01

SNMP traps (fallback)

The item is used to collect all SNMP traps unmatched by other snmptrap items

SNMP trap snmptrap.fallback
System location

MIB: SNMPv2-MIB

The physical location of this node (e.g., `telephone closet, 3rd floor'). If the location is unknown, the value is the zero-length string.

SNMP agent system.location[sysLocation.0]

Preprocessing

  • Discard unchanged with heartbeat: 6h

System contact details

MIB: SNMPv2-MIB

The textual identification of the contact person for this managed

node, together with information on how to contact this person. If no contact

information is known, the value is the zero-length string.

SNMP agent system.contact[sysContact.0]

Preprocessing

  • Discard unchanged with heartbeat: 12h

System object ID

MIB: SNMPv2-MIB

The vendor's authoritative identification of the network management subsystem contained in the entity. This value is allocated within the SMI enterprises subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determiningwhat kind of box' is being managed. For example, if vendorFlintstones, Inc.' was assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1 to its `Fred Router'.

SNMP agent system.objectid[sysObjectID.0]

Preprocessing

  • Discard unchanged with heartbeat: 6h

System name

MIB: SNMPv2-MIB

An administratively-assigned name for this managed node.By convention, this is the node's fully-qualified domain name. If the name is unknown, the value is the zero-length string.

SNMP agent system.name[sysName.0]

Preprocessing

  • Discard unchanged with heartbeat: 6h

System description

MIB: SNMPv2-MIB

A textual description of the entity. This value should

include the full name and version identification of the system's hardware type, software operating-system, and

networking software.

SNMP agent system.descr[sysDescr.0]

Preprocessing

  • Discard unchanged with heartbeat: 12h

SNMP agent availability

Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list.

Possible values:

0 - not available

1 - available

2 - unknown

Zabbix internal zabbix[host,snmp,available]

Preprocessing

  • Discard unchanged with heartbeat: 6h

Triggers

Name Description Expression Severity Dependencies and additional info
APC Smart-UPS: Battery has an internal error condition

A battery installed has an internal error condition.

last(/APC Smart-UPS SRT 5000 by SNMP/battery.status[upsBasicBatteryStatus])=4 Average
APC Smart-UPS: Battery is Low

The UPS will be unable to sustain the current load, and its services will be lost if power is not restored.

last(/APC Smart-UPS SRT 5000 by SNMP/battery.status[upsBasicBatteryStatus])=3 Average
APC Smart-UPS: Battery has low capacity last(/APC Smart-UPS SRT 5000 by SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN} High
APC Smart-UPS: Battery needs replacement

A battery installed has an internal error condition.

last(/APC Smart-UPS SRT 5000 by SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2 High
APC Smart-UPS: Battery has high temperature min(/APC Smart-UPS SRT 5000 by SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN} High
APC Smart-UPS: Unacceptable input voltage min(/APC Smart-UPS SRT 5000 by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS SRT 5000 by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 5000 by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}) High
APC Smart-UPS: Unacceptable input frequency min(/APC Smart-UPS SRT 5000 by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS SRT 5000 by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS SRT 5000 by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN}) High
APC Smart-UPS: Output load is high

A battery installed has an internal error condition.

min(/APC Smart-UPS SRT 5000 by SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN} High
APC Smart-UPS: UPS is Timed Sleeping last(/APC Smart-UPS SRT 5000 by SNMP/output.status[upsBasicOutputStatus])=5 Average
APC Smart-UPS: UPS is Switched Bypass last(/APC Smart-UPS SRT 5000 by SNMP/output.status[upsBasicOutputStatus])=9 Average
APC Smart-UPS: UPS is Software Bypass last(/APC Smart-UPS SRT 5000 by SNMP/output.status[upsBasicOutputStatus])=6 Average
APC Smart-UPS: UPS is Sleeping Until Power Return last(/APC Smart-UPS SRT 5000 by SNMP/output.status[upsBasicOutputStatus])=11 Average
APC Smart-UPS: UPS is Rebooting last(/APC Smart-UPS SRT 5000 by SNMP/output.status[upsBasicOutputStatus])=8 Average
APC Smart-UPS: UPS is On Smart Trim last(/APC Smart-UPS SRT 5000 by SNMP/output.status[upsBasicOutputStatus])=12 Average
APC Smart-UPS: UPS is on Smart Boost last(/APC Smart-UPS SRT 5000 by SNMP/output.status[upsBasicOutputStatus])=4 Average
APC Smart-UPS: UPS is on battery last(/APC Smart-UPS SRT 5000 by SNMP/output.status[upsBasicOutputStatus])=3 Average
APC Smart-UPS: UPS is Off last(/APC Smart-UPS SRT 5000 by SNMP/output.status[upsBasicOutputStatus])=7 Average
APC Smart-UPS: UPS is Emergency Static Bypass last(/APC Smart-UPS SRT 5000 by SNMP/output.status[upsBasicOutputStatus])=16 Average
APC Smart-UPS: UPS is Hardware Failure Bypass last(/APC Smart-UPS SRT 5000 by SNMP/output.status[upsBasicOutputStatus])=10 Average
APC Smart-UPS: Host has been restarted

Uptime is less than 10 minutes.

(last(/APC Smart-UPS SRT 5000 by SNMP/system.hw.uptime[hrSystemUptime.0])>0 and last(/APC Smart-UPS SRT 5000 by SNMP/system.hw.uptime[hrSystemUptime.0])<10m) or (last(/APC Smart-UPS SRT 5000 by SNMP/system.hw.uptime[hrSystemUptime.0])=0 and last(/APC Smart-UPS SRT 5000 by SNMP/system.net.uptime[sysUpTime.0])<10m) Warning Manual close: Yes
Depends on:
  • APC Smart-UPS: No SNMP data collection
APC Smart-UPS: System name has changed

The name of the system has changed. Acknowledge to close the problem manually.

last(/APC Smart-UPS SRT 5000 by SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS SRT 5000 by SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS SRT 5000 by SNMP/system.name[sysName.0]))>0 Info Manual close: Yes
APC Smart-UPS: No SNMP data collection

SNMP is not available for polling. Please check device connectivity and SNMP settings.

max(/APC Smart-UPS SRT 5000 by SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0 Warning

LLD rule Input phases discovery

Name Description Type Key and additional info
Input phases discovery

The input phase identifier. OID upsPhaseInputPhaseIndex.1.1

SNMP agent input.phases.discovery

Item prototypes for Input phases discovery

Name Description Type Key and additional info
{#PHASEINDEX}: Phase input voltage

MIB: PowerNet-MIB

The input voltage in VAC, or -1 if it's unsupported

by this UPS.

SNMP agent phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]

Preprocessing

  • Discard unchanged with heartbeat: 6h

{#PHASEINDEX}: Phase input current

MIB: PowerNet-MIB

The input current in 0.1 amperes, or -0.1 if it's

unsupported by this UPS.

SNMP agent phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]

Preprocessing

  • Custom multiplier: 0.1

  • Discard unchanged with heartbeat: 6h

Trigger prototypes for Input phases discovery

Name Description Expression Severity Dependencies and additional info
APC Smart-UPS: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage min(/APC Smart-UPS SRT 5000 by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 5000 by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN} High

LLD rule Output phases discovery

Name Description Type Key and additional info
Output phases discovery

The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1

SNMP agent output.phases.discovery

Item prototypes for Output phases discovery

Name Description Type Key and additional info
{#PHASEINDEX}: Phase output voltage

MIB: PowerNet-MIB

The output voltage in VAC, or -1 if it's unsupported

by this UPS.

SNMP agent phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]

Preprocessing

  • Discard unchanged with heartbeat: 6h

{#PHASEINDEX}: Phase output current

MIB: PowerNet-MIB

The output current in 0.1 amperes drawn

by the load on the UPS, or -1 if it's unsupported

by this UPS.

SNMP agent phase.output.current[upsPhaseOutputCurrent.1.1.{#PHASEINDEX}]

Preprocessing

  • Custom multiplier: 0.1

  • Discard unchanged with heartbeat: 6h

{#PHASEINDEX}: Phase output load, %

MIB: PowerNet-MIB

The percentage of the UPS load capacity in VA at

redundancy @ (n + x) presently being used on this

output phase, or -1 if it's unsupported by this UPS.

SNMP agent phase.output.load.percent[upsPhaseOutputPercentLoad.1.1.{#PHASEINDEX}]

Preprocessing

  • Discard unchanged with heartbeat: 6h

Trigger prototypes for Output phases discovery

Name Description Expression Severity Dependencies and additional info
APC Smart-UPS: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage min(/APC Smart-UPS SRT 5000 by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS SRT 5000 by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN} High

LLD rule External battery packs discovery

Name Description Type Key and additional info
External battery packs discovery SNMP agent battery.packs.discovery

Item prototypes for External battery packs discovery

Name Description Type Key and additional info
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status

MIB: PowerNet-MIB

The status of the UPS batteries. A batteryLow(3) value

indicates the UPS will be unable to sustain the current

load, and its services will be lost if power is not restored.

The amount of run time in reserve at the time of low battery

can be configured by the upsAdvConfigLowBatteryRunTime.

A batteryInFaultCondition(4)value indicates that a battery

installed has an internal error condition.

SNMP agent battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]

Preprocessing

  • Discard unchanged with heartbeat: 6h

{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery temperature

MIB: PowerNet-MIB

The current internal UPS temperature in Celsius.

Temperatures below zero read as 0.

SNMP agent battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]

Preprocessing

  • Custom multiplier: 0.1

  • Discard unchanged with heartbeat: 6h

{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number

MIB: PowerNet-MIB

An 8-character string identifying the serial number of

the UPS internal microprocessor. This number is set at

the factory. NOTE: This number does NOT correspond to

the serial number on the rear of the UPS.

SNMP agent system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]

Preprocessing

  • Discard unchanged with heartbeat: 6h

{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery estimated replace date

MIB: PowerNet-MIB

The battery cartridge estimated battery replace date.

SNMP agent battery.estimated_replace_date[upsHighPrecBatteryPackCartridgeReplaceDate.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]

Preprocessing

  • Discard unchanged with heartbeat: 6h

{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health

MIB: PowerNet-MIB

The battery cartridge health.

bit 0 Battery lifetime okay

bit 1 Battery lifetime near end, order replacement cartridge

bit 2 Battery lifetime exceeded, replace battery

bit 3 Battery lifetime near end acknowledged, order replacement cartridge

bit 4 Battery lifetime exceeded acknowledged, replace battery

bit 5 Battery measured lifetime near end, order replacement cartridge

bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge

SNMP agent battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]

Preprocessing

  • Discard unchanged with heartbeat: 6h

Trigger prototypes for External battery packs discovery

Name Description Expression Severity Dependencies and additional info
APC Smart-UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay

The battery cartridge status:
bit 0 Disconnected
bit 1 Overvoltage
bit 2 NeedsReplacement
bit 3 OvertemperatureCritical
bit 4 Charger
bit 5 TemperatureSensor
bit 6 BusSoftStart
bit 7 OvertemperatureWarning
bit 8 GeneralError
bit 9 Communication
bit 10 DisconnectedFrame
bit 11 FirmwareMismatch

find(/APC Smart-UPS SRT 5000 by SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0 Warning
APC Smart-UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature min(/APC Smart-UPS SRT 5000 by SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN} High
APC Smart-UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay

The battery cartridge health.
bit 0 Battery lifetime okay
bit 1 Battery lifetime near end, order replacement cartridge
bit 2 Battery lifetime exceeded, replace battery
bit 3 Battery lifetime near end acknowledged, order replacement cartridge
bit 4 Battery lifetime exceeded acknowledged, replace battery
bit 5 Battery measured lifetime near end, order replacement cartridge
bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge

find(/APC Smart-UPS SRT 5000 by SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1 Warning

LLD rule External bad battery packs discovery

Name Description Type Key and additional info
External bad battery packs discovery

Discovery of the number of external defective battery packs.

SNMP agent battery.packs.bad.discovery

Item prototypes for External bad battery packs discovery

Name Description Type Key and additional info
{#SNMPINDEX}: External battery packs bad

MIB: PowerNet-MIB

The number of external battery packs connected to the UPS that

are defective. If the UPS does not use smart cells then the

agent reports ERROR_NO_SUCH_NAME.

SNMP agent battery.external_packs_bad[upsAdvBatteryNumOfBadBattPacks.{#SNMPINDEX}]

Preprocessing

  • Discard unchanged with heartbeat: 6h

LLD rule External sensor port 1 discovery

Name Description Type Key and additional info
External sensor port 1 discovery

uioSensorStatusTable

SNMP agent external.sensor1.discovery

Item prototypes for External sensor port 1 discovery

Name Description Type Key and additional info
{#EXTERNAL_SENSOR1_NAME}: Temperature sensor

MIB: PowerNet-MIB

The sensor's current temperature reading in Celsius.

-1 indicates an invalid reading due to lost communications.

SNMP agent external.sensor.temperature[uioSensorStatusTemperatureDegC.1.{#SNMPINDEX}]

Preprocessing

  • Discard unchanged with heartbeat: 6h

{#EXTERNAL_SENSOR1_NAME}: Humidity sensor

MIB: PowerNet-MIB

The sensor's current humidity reading - a relative humidity

percentage. -1 indicates an invalid reading due to either a

sensor that doesn't read humidity or lost communications.

SNMP agent external.sensor.humidity[uioSensorStatusHumidity.1.{#SNMPINDEX}]

Preprocessing

  • Discard unchanged with heartbeat: 6h

{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status

MIB: PowerNet-MIB

The alarm status of the sensor. Possible values:

uioNormal (1),

uioWarning (2),

uioCritical (3),

sensorStatusNotApplicable (4)

SNMP agent external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}]

Preprocessing

  • Discard unchanged with heartbeat: 6h

Trigger prototypes for External sensor port 1 discovery

Name Description Expression Severity Dependencies and additional info
APC Smart-UPS: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable

The external sensor does not work or is not connected.

last(/APC Smart-UPS SRT 5000 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4 Info
APC Smart-UPS: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning

The external sensor has returned a value greater than the warning threshold.

last(/APC Smart-UPS SRT 5000 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2 Average
APC Smart-UPS: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical

The external sensor has returned a value greater than the critical threshold.

last(/APC Smart-UPS SRT 5000 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3 High

LLD rule External sensor port 2 discovery

Name Description Type Key and additional info
External sensor port 2 discovery

uioSensorStatusTable

SNMP agent external.sensor2.discovery

Item prototypes for External sensor port 2 discovery

Name Description Type Key and additional info
{#EXTERNAL_SENSOR2_NAME}: Temperature sensor

MIB: PowerNet-MIB

The sensor's current temperature reading in Celsius.

-1 indicates an invalid reading due to lost communications.

SNMP agent external.sensor.temperature[uioSensorStatusTemperatureDegC.2.{#SNMPINDEX}]

Preprocessing

  • Discard unchanged with heartbeat: 6h

{#EXTERNAL_SENSOR2_NAME}: Humidity sensor

MIB: PowerNet-MIB

The sensor's current humidity reading - a relative humidity

percentage. -1 indicates an invalid reading due to either a

sensor that doesn't read humidity or lost communications.

SNMP agent external.sensor.humidity[uioSensorStatusHumidity.2.{#SNMPINDEX}]

Preprocessing

  • Discard unchanged with heartbeat: 6h

{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status

MIB: PowerNet-MIB

The alarm status of the sensor. Possible values:

uioNormal (1),

uioWarning (2),

uioCritical (3),

sensorStatusNotApplicable (4)

SNMP agent external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}]

Preprocessing

  • Discard unchanged with heartbeat: 6h

Trigger prototypes for External sensor port 2 discovery

Name Description Expression Severity Dependencies and additional info
APC Smart-UPS: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable

The external sensor does not work or is not connected.

last(/APC Smart-UPS SRT 5000 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4 Info
APC Smart-UPS: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning

The external sensor has returned a value greater than the warning threshold.

last(/APC Smart-UPS SRT 5000 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2 Average
APC Smart-UPS: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical

The external sensor has returned a value greater than the critical threshold.

last(/APC Smart-UPS SRT 5000 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3 High

Feedback

Please report any issues with the template at https://support.zabbix.com

You can also provide feedback, discuss the template, or ask for help at ZABBIX forums

Articles and documentation

+ Propose new article

No se encuentra la integración que necesitas?