The template to monitor APC Smart-UPS RT 1000 XL by Zabbix SNMP agent. Note: please, use the latest version of the firmware for your NMC in order for the template to work correctly.
Zabbix version: 7.2 and higher.
This template has been tested on:
Zabbix should be configured according to the instructions in the Templates out of the box section.
1. Create a host for APC Smart-UPS RT 1000 XL management IP as SNMPv2 interface.
2. Link the template to the host.
3. Customize macro values if needed.
Name | Description | Default |
---|---|---|
{$BATTERY.TEMP.MAX.WARN} | Maximum battery temperature for trigger expression. |
55 |
{$BATTERY.CAPACITY.MIN.WARN} | Minimum battery capacity percentage for trigger expression. |
50 |
{$UPS.OUTPUT.MAX.WARN} | Maximum output load in % for trigger expression. |
80 |
{$UPS.INPUT_FREQ.MIN.WARN} | Minimum input frequency for trigger expression. |
49.7 |
{$UPS.INPUT_FREQ.MAX.WARN} | Maximum input frequency for trigger expression. |
50.3 |
{$UPS.INPUT_VOLT.MIN.WARN} | Minimum input voltage for trigger expression. |
197 |
{$UPS.INPUT_VOLT.MAX.WARN} | Maximum input voltage for trigger expression. |
243 |
{$TIME.PERIOD} | Time period for trigger expression. |
15m |
{$SNMP.TIMEOUT} | The time interval for SNMP agent availability trigger expression. |
5m |
Name | Description | Type | Key and additional info |
---|---|---|---|
Model | MIB: PowerNet-MIB The UPS model name (e.g. 'APC Smart-UPS 600'). |
SNMP agent | system.model[upsBasicIdentModel] Preprocessing
|
Serial number | MIB: PowerNet-MIB An 8-character string identifying the serial number of the UPS internal microprocessor. This number is set at the factory. NOTE: This number does NOT correspond to the serial number on the rear of the UPS. |
SNMP agent | system.sn[upsAdvIdentSerialNumber] Preprocessing
|
Battery status | MIB: PowerNet-MIB The status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored. The amount of run time in reserve at the time of low battery can be configured by the upsAdvConfigLowBatteryRunTime. A batteryInFaultCondition(4)value indicates that a battery installed has an internal error condition. |
SNMP agent | battery.status[upsBasicBatteryStatus] Preprocessing
|
Battery capacity | MIB: PowerNet-MIB The remaining battery capacity expressed as percentage of full capacity. |
SNMP agent | battery.capacity[upsHighPrecBatteryCapacity] Preprocessing
|
Battery runtime remaining | MIB: PowerNet-MIB The UPS battery run time remaining before battery exhaustion. |
SNMP agent | battery.runtime_remaining[upsAdvBatteryRunTimeRemaining] Preprocessing
|
Battery voltage | MIB: PowerNet-MIB The actual battery bus voltage in Volts. |
SNMP agent | battery.voltage[upsHighPrecBatteryActualVoltage] Preprocessing
|
Battery last replace date | MIB: PowerNet-MIB The date when the UPS system's batteries were last replaced in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value is originally set at the factory. When the UPS batteries are replaced, this value should be reset by the administrator. For Symmetra PX 250/500 this OID is read-only and is configurable in the local display only. |
SNMP agent | battery.last_replace_date[upsBasicBatteryLastReplaceDate] Preprocessing
|
Battery replace indicator | MIB: PowerNet-MIB Indicates whether the UPS batteries need replacement. |
SNMP agent | battery.replace_indicator[upsAdvBatteryReplaceIndicator] Preprocessing
|
External battery packs count | MIB: PowerNet-MIB The number of external battery packs connected to the UPS. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME. |
SNMP agent | battery.external_packs_count[upsAdvBatteryNumOfBattPacks] Preprocessing
|
Battery temperature | MIB: PowerNet-MIB The current internal UPS temperature in Celsius. Temperatures below zero read as 0. |
SNMP agent | battery.temperature[upsHighPrecBatteryTemperature] Preprocessing
|
Input voltage | MIB: PowerNet-MIB The current utility line voltage in VAC. |
SNMP agent | input.voltage[upsHighPrecInputLineVoltage] Preprocessing
|
Input frequency | MIB: PowerNet-MIB The current input frequency to the UPS system in Hz. |
SNMP agent | input.frequency[upsHighPrecInputFrequency] Preprocessing
|
Input fail cause | MIB: PowerNet-MIB The reason for the occurrence of the last transfer to UPS battery power. The variable is set to: - noTransfer(1) -- if there is no transfer yet. - highLineVoltage(2) -- if the transfer to battery is caused by an over voltage greater than the high transfer voltage. - brownout(3) -- if the duration of the outage is greater than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - blackout(4) -- if the duration of the outage is greater than five seconds and the line voltage is between 40% of the rated output voltage and ground. - smallMomentarySag(5) -- if the duration of the outage is less than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - deepMomentarySag(6) -- if the duration of the outage is less than five seconds and the line voltage is between 40% of the rated output voltage and ground. The variable is set to - smallMomentarySpike(7) -- if the line failure is caused by a rate of change of input voltage less than ten volts per cycle. - largeMomentarySpike(8) -- if the line failure is caused by a rate of change of input voltage greater than ten volts per cycle. - selfTest(9) -- if the UPS was commanded to do a self test. - rateOfVoltageChange(10) -- if the failure is due to the rate of change of the line voltage. |
SNMP agent | input.fail[upsAdvInputLineFailCause] Preprocessing
|
Output voltage | MIB: PowerNet-MIB The output voltage of the UPS system in VAC. |
SNMP agent | output.voltage[upsHighPrecOutputVoltage] Preprocessing
|
Output load | MIB: PowerNet-MIB The current UPS load expressed as percentage of rated capacity. |
SNMP agent | output.load[upsHighPrecOutputLoad] Preprocessing
|
Output current | MIB: PowerNet-MIB The current in amperes drawn by the load on the UPS. |
SNMP agent | output.current[upsHighPrecOutputCurrent] Preprocessing
|
Output status | MIB: PowerNet-MIB The current state of the UPS. If the UPS is unable to determine the state of the UPS this variable is set to unknown(1). During self-test most UPSes report onBattery(3) but some that support it will report onBatteryTest(15). To determine self-test status across all UPSes, refer to the upsBasicStateOutputState OID. |
SNMP agent | output.status[upsBasicOutputStatus] Preprocessing
|
Uptime (network) | MIB: SNMPv2-MIB The time (in hundredths of a second) since the network management portion of the system was last re-initialized. |
SNMP agent | system.net.uptime[sysUpTime.0] Preprocessing
|
Uptime (hardware) | MIB: HOST-RESOURCES-MIB The amount of time since this host was last initialized. Note that this is different from sysUpTime in the SNMPv2-MIB [RFC1907] because sysUpTime is the uptime of the network management portion of the system. |
SNMP agent | system.hw.uptime[hrSystemUptime.0] Preprocessing
|
SNMP traps (fallback) | The item is used to collect all SNMP traps unmatched by other snmptrap items |
SNMP trap | snmptrap.fallback |
System location | MIB: SNMPv2-MIB The physical location of this node (e.g., `telephone closet, 3rd floor'). If the location is unknown, the value is the zero-length string. |
SNMP agent | system.location[sysLocation.0] Preprocessing
|
System contact details | MIB: SNMPv2-MIB The textual identification of the contact person for this managed node, together with information on how to contact this person. If no contact information is known, the value is the zero-length string. |
SNMP agent | system.contact[sysContact.0] Preprocessing
|
System object ID | MIB: SNMPv2-MIB The vendor's authoritative identification of the network management subsystem contained in the entity. This value is allocated within the SMI enterprises subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining |
SNMP agent | system.objectid[sysObjectID.0] Preprocessing
|
System name | MIB: SNMPv2-MIB An administratively-assigned name for this managed node.By convention, this is the node's fully-qualified domain name. If the name is unknown, the value is the zero-length string. |
SNMP agent | system.name[sysName.0] Preprocessing
|
System description | MIB: SNMPv2-MIB A textual description of the entity. This value should include the full name and version identification of the system's hardware type, software operating-system, and networking software. |
SNMP agent | system.descr[sysDescr.0] Preprocessing
|
SNMP agent availability | Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list. Possible values: 0 - not available 1 - available 2 - unknown |
Zabbix internal | zabbix[host,snmp,available] Preprocessing
|
Name | Description | Expression | Severity | Dependencies and additional info |
---|---|---|---|---|
APC Smart-UPS: Battery has an internal error condition | A battery installed has an internal error condition. |
last(/APC Smart-UPS RT 1000 XL by SNMP/battery.status[upsBasicBatteryStatus])=4 |
Average | |
APC Smart-UPS: Battery is Low | The UPS will be unable to sustain the current load, and its services will be lost if power is not restored. |
last(/APC Smart-UPS RT 1000 XL by SNMP/battery.status[upsBasicBatteryStatus])=3 |
Average | |
APC Smart-UPS: Battery has low capacity | last(/APC Smart-UPS RT 1000 XL by SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN} |
High | ||
APC Smart-UPS: Battery needs replacement | A battery installed has an internal error condition. |
last(/APC Smart-UPS RT 1000 XL by SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2 |
High | |
APC Smart-UPS: Battery has high temperature | min(/APC Smart-UPS RT 1000 XL by SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN} |
High | ||
APC Smart-UPS: Unacceptable input voltage | min(/APC Smart-UPS RT 1000 XL by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 XL by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}) |
High | ||
APC Smart-UPS: Unacceptable input frequency | min(/APC Smart-UPS RT 1000 XL by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC Smart-UPS RT 1000 XL by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN}) |
High | ||
APC Smart-UPS: Output load is high | A battery installed has an internal error condition. |
min(/APC Smart-UPS RT 1000 XL by SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN} |
High | |
APC Smart-UPS: UPS is Timed Sleeping | last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=5 |
Average | ||
APC Smart-UPS: UPS is Switched Bypass | last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=9 |
Average | ||
APC Smart-UPS: UPS is Software Bypass | last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=6 |
Average | ||
APC Smart-UPS: UPS is Sleeping Until Power Return | last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=11 |
Average | ||
APC Smart-UPS: UPS is Rebooting | last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=8 |
Average | ||
APC Smart-UPS: UPS is On Smart Trim | last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=12 |
Average | ||
APC Smart-UPS: UPS is on Smart Boost | last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=4 |
Average | ||
APC Smart-UPS: UPS is on battery | last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=3 |
Average | ||
APC Smart-UPS: UPS is Off | last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=7 |
Average | ||
APC Smart-UPS: UPS is Emergency Static Bypass | last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=16 |
Average | ||
APC Smart-UPS: UPS is Hardware Failure Bypass | last(/APC Smart-UPS RT 1000 XL by SNMP/output.status[upsBasicOutputStatus])=10 |
Average | ||
APC Smart-UPS: Host has been restarted | Uptime is less than 10 minutes. |
(last(/APC Smart-UPS RT 1000 XL by SNMP/system.hw.uptime[hrSystemUptime.0])>0 and last(/APC Smart-UPS RT 1000 XL by SNMP/system.hw.uptime[hrSystemUptime.0])<10m) or (last(/APC Smart-UPS RT 1000 XL by SNMP/system.hw.uptime[hrSystemUptime.0])=0 and last(/APC Smart-UPS RT 1000 XL by SNMP/system.net.uptime[sysUpTime.0])<10m) |
Warning | Manual close: Yes Depends on:
|
APC Smart-UPS: System name has changed | The name of the system has changed. Acknowledge to close the problem manually. |
last(/APC Smart-UPS RT 1000 XL by SNMP/system.name[sysName.0],#1)<>last(/APC Smart-UPS RT 1000 XL by SNMP/system.name[sysName.0],#2) and length(last(/APC Smart-UPS RT 1000 XL by SNMP/system.name[sysName.0]))>0 |
Info | Manual close: Yes |
APC Smart-UPS: No SNMP data collection | SNMP is not available for polling. Please check device connectivity and SNMP settings. |
max(/APC Smart-UPS RT 1000 XL by SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0 |
Warning |
Name | Description | Type | Key and additional info |
---|---|---|---|
Input phases discovery | The input phase identifier. OID upsPhaseInputPhaseIndex.1.1 |
SNMP agent | input.phases.discovery |
Name | Description | Type | Key and additional info |
---|---|---|---|
{#PHASEINDEX}: Phase input voltage | MIB: PowerNet-MIB The input voltage in VAC, or -1 if it's unsupported by this UPS. |
SNMP agent | phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}] Preprocessing
|
{#PHASEINDEX}: Phase input current | MIB: PowerNet-MIB The input current in 0.1 amperes, or -0.1 if it's unsupported by this UPS. |
SNMP agent | phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}] Preprocessing
|
Name | Description | Expression | Severity | Dependencies and additional info |
---|---|---|---|---|
APC Smart-UPS: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage | min(/APC Smart-UPS RT 1000 XL by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN} |
High |
Name | Description | Type | Key and additional info |
---|---|---|---|
Output phases discovery | The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1 |
SNMP agent | output.phases.discovery |
Name | Description | Type | Key and additional info |
---|---|---|---|
{#PHASEINDEX}: Phase output voltage | MIB: PowerNet-MIB The output voltage in VAC, or -1 if it's unsupported by this UPS. |
SNMP agent | phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}] Preprocessing
|
{#PHASEINDEX}: Phase output current | MIB: PowerNet-MIB The output current in 0.1 amperes drawn by the load on the UPS, or -1 if it's unsupported by this UPS. |
SNMP agent | phase.output.current[upsPhaseOutputCurrent.1.1.{#PHASEINDEX}] Preprocessing
|
{#PHASEINDEX}: Phase output load, % | MIB: PowerNet-MIB The percentage of the UPS load capacity in VA at redundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this UPS. |
SNMP agent | phase.output.load.percent[upsPhaseOutputPercentLoad.1.1.{#PHASEINDEX}] Preprocessing
|
Name | Description | Expression | Severity | Dependencies and additional info |
---|---|---|---|---|
APC Smart-UPS: {#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage | min(/APC Smart-UPS RT 1000 XL by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC Smart-UPS RT 1000 XL by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN} |
High |
Name | Description | Type | Key and additional info |
---|---|---|---|
External battery packs discovery | SNMP agent | battery.packs.discovery |
Name | Description | Type | Key and additional info |
---|---|---|---|
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status | MIB: PowerNet-MIB The status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored. The amount of run time in reserve at the time of low battery can be configured by the upsAdvConfigLowBatteryRunTime. A batteryInFaultCondition(4)value indicates that a battery installed has an internal error condition. |
SNMP agent | battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}] Preprocessing
|
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery temperature | MIB: PowerNet-MIB The current internal UPS temperature in Celsius. Temperatures below zero read as 0. |
SNMP agent | battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}] Preprocessing
|
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number | MIB: PowerNet-MIB An 8-character string identifying the serial number of the UPS internal microprocessor. This number is set at the factory. NOTE: This number does NOT correspond to the serial number on the rear of the UPS. |
SNMP agent | system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}] Preprocessing
|
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery estimated replace date | MIB: PowerNet-MIB The battery cartridge estimated battery replace date. |
SNMP agent | battery.estimated_replace_date[upsHighPrecBatteryPackCartridgeReplaceDate.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}] Preprocessing
|
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health | MIB: PowerNet-MIB The battery cartridge health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement cartridge bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replacement cartridge bit 4 Battery lifetime exceeded acknowledged, replace battery bit 5 Battery measured lifetime near end, order replacement cartridge bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge |
SNMP agent | battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}] Preprocessing
|
Name | Description | Expression | Severity | Dependencies and additional info |
---|---|---|---|---|
APC Smart-UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay | The battery cartridge status: |
find(/APC Smart-UPS RT 1000 XL by SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0 |
Warning | |
APC Smart-UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature | min(/APC Smart-UPS RT 1000 XL by SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN} |
High | ||
APC Smart-UPS: {#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay | The battery cartridge health. |
find(/APC Smart-UPS RT 1000 XL by SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1 |
Warning |
Name | Description | Type | Key and additional info |
---|---|---|---|
External bad battery packs discovery | Discovery of the number of external defective battery packs. |
SNMP agent | battery.packs.bad.discovery |
Name | Description | Type | Key and additional info |
---|---|---|---|
{#SNMPINDEX}: External battery packs bad | MIB: PowerNet-MIB The number of external battery packs connected to the UPS that are defective. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME. |
SNMP agent | battery.external_packs_bad[upsAdvBatteryNumOfBadBattPacks.{#SNMPINDEX}] Preprocessing
|
Name | Description | Type | Key and additional info |
---|---|---|---|
External sensor port 1 discovery | uioSensorStatusTable |
SNMP agent | external.sensor1.discovery |
Name | Description | Type | Key and additional info |
---|---|---|---|
{#EXTERNAL_SENSOR1_NAME}: Temperature sensor | MIB: PowerNet-MIB The sensor's current temperature reading in Celsius. -1 indicates an invalid reading due to lost communications. |
SNMP agent | external.sensor.temperature[uioSensorStatusTemperatureDegC.1.{#SNMPINDEX}] Preprocessing
|
{#EXTERNAL_SENSOR1_NAME}: Humidity sensor | MIB: PowerNet-MIB The sensor's current humidity reading - a relative humidity percentage. -1 indicates an invalid reading due to either a sensor that doesn't read humidity or lost communications. |
SNMP agent | external.sensor.humidity[uioSensorStatusHumidity.1.{#SNMPINDEX}] Preprocessing
|
{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status | MIB: PowerNet-MIB The alarm status of the sensor. Possible values: uioNormal (1), uioWarning (2), uioCritical (3), sensorStatusNotApplicable (4) |
SNMP agent | external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}] Preprocessing
|
Name | Description | Expression | Severity | Dependencies and additional info |
---|---|---|---|---|
APC Smart-UPS: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable | The external sensor does not work or is not connected. |
last(/APC Smart-UPS RT 1000 XL by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4 |
Info | |
APC Smart-UPS: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning | The external sensor has returned a value greater than the warning threshold. |
last(/APC Smart-UPS RT 1000 XL by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2 |
Average | |
APC Smart-UPS: {#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical | The external sensor has returned a value greater than the critical threshold. |
last(/APC Smart-UPS RT 1000 XL by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3 |
High |
Name | Description | Type | Key and additional info |
---|---|---|---|
External sensor port 2 discovery | uioSensorStatusTable |
SNMP agent | external.sensor2.discovery |
Name | Description | Type | Key and additional info |
---|---|---|---|
{#EXTERNAL_SENSOR2_NAME}: Temperature sensor | MIB: PowerNet-MIB The sensor's current temperature reading in Celsius. -1 indicates an invalid reading due to lost communications. |
SNMP agent | external.sensor.temperature[uioSensorStatusTemperatureDegC.2.{#SNMPINDEX}] Preprocessing
|
{#EXTERNAL_SENSOR2_NAME}: Humidity sensor | MIB: PowerNet-MIB The sensor's current humidity reading - a relative humidity percentage. -1 indicates an invalid reading due to either a sensor that doesn't read humidity or lost communications. |
SNMP agent | external.sensor.humidity[uioSensorStatusHumidity.2.{#SNMPINDEX}] Preprocessing
|
{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status | MIB: PowerNet-MIB The alarm status of the sensor. Possible values: uioNormal (1), uioWarning (2), uioCritical (3), sensorStatusNotApplicable (4) |
SNMP agent | external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}] Preprocessing
|
Name | Description | Expression | Severity | Dependencies and additional info |
---|---|---|---|---|
APC Smart-UPS: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable | The external sensor does not work or is not connected. |
last(/APC Smart-UPS RT 1000 XL by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4 |
Info | |
APC Smart-UPS: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning | The external sensor has returned a value greater than the warning threshold. |
last(/APC Smart-UPS RT 1000 XL by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2 |
Average | |
APC Smart-UPS: {#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical | The external sensor has returned a value greater than the critical threshold. |
last(/APC Smart-UPS RT 1000 XL by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3 |
High |
Please report any issues with the template at https://support.zabbix.com
You can also provide feedback, discuss the template, or ask for help at ZABBIX forums